Laureate
Series Digital Panel Meters
Programmable 1/8 DIN-size
meter / controllers for DC voltage & current, AC RMS voltage & current,
process (e.g., 4-20 mA), strain, potentiometer follower, load cell, microvolt, scale meter
(weight), temperature (thermocouple & RTD).
To configure and price out
an instrument, select Quantity, press on the radio buttons below,
then on "Add items to shopping
cart. If you wish to construct a model number
so that your company can issue a purchase order, combine the radio
button selections to create a
model number in this format: L10010DCV1. This example calls out a
Laureate panel
meter with a standard main board with green LEDs, 95-240 Vac &
95-300 Vdc power, no setpoint output, 0-20 mA & 0-10 V analog
outputs, no digital interface, and a DC signal conditioner set for ±200.00 mV.
Includes plug-in screw terminals.
|
| |
Laureate Digital Panel Meter |
Quantity
|
|
DPM
Type |
L Digital
Panel Meter. |
$220 |
Main
Board |
1 Standard Main Board, Green LEDs.
2 Standard
Main Board, Red LEDs.
3
Extended
Main Board, Green LEDs.
4
Extended Main Board,
Red LEDs. |
NC
NC
$40
$40 |
| |
Note:
Extended capability is required for custom curve linearization or for display of time rate
of change, such as flow rate from changing tank level or acceleration from changing speed.
Not applicable to temperature. |
|
| Power |
0 Isolated 95-240
Vac & 95-300 Vdc
1
Isolated 10-34 Vac
& 10-48 Vdc. |
NC
$30 |
Setpoint
Output |
0 None.
1 Dual
8A Contact Relays.
2 Isolated Dual Solid State Relays. |
NC
$80
$55 |
Analog
Output |
0 None.
1 Isolated 0-20 mA & 0-10 V. |
NC
$90 |
Digital
Interface |
0 None.
1 Isolated RS-232.
2 Isolated RS-485.
4 Isolated RS-485 Modbus. |
NC
$60
$80
$90 |
Signal
Input |
DC
Volts
DCV1
±200.00 mV.
DCV2
±2.0000 V.
DCV3
±20.000 V.
DCV4
±200.00 V.
DCV5
±300.0 V. |
NC |
DC
Amps
DCA1
±2.0000 mA.
DCA2
±20.000 mA.
DCA3
±200.00 mA.
DCA4
±5.000 A. |
NC |
Process
Signals (e.g., 4-20 mA, 0-5 V)
P Default
Scaling. 4-20 mA = 0-100.00.
P1 Custom
Scaling.
In the write-in field of your invoice, specify min input, min reading; max input, max
reading. |
NC
$10 |
Strain
Gage, Potentiometer (4-wire ratio)
SG
Default
Scaling. 0-200 mV = 0-100.00.
SG1
Custom
Scaling.
In the write-in field of your invoice, specify min input, min reading; max input, max
reading. |
NC
$10 |
| Note:
The same DC signal conditioner board can be user-configured for DC Volts, DC Amps,
process, or strain. It is precalibrated in EEPROM for all DC Volt and DC Amp ranges
listed. |
|
True
AC RMS Volts
RMV1
200.00 mV.
RMV2
2.0000 V.
RMV3
20.000 V.
RMV4
200.00 V.
RMV5
600.0 V (range is not UL approved).
RMV6
250.0 V. |
$35 |
True
AC RMS Amps
RMA1
2.0000 mA.
RMA2
20.000 mA.
RMA3
200.00 mA.
RMA4
5.000 A. |
$35 |
| Note:
The same AC RMS signal conditioner can be user configured for AC Volts or AC Amps. It is
precalibrated in EEPROM for all AC Volt and AC Amp ranges listed. |
|
Thermocouples
JC Thermocouple Type J, -210°C to
760°C.
JF Thermocouple Type J, -347°F to
1400°F.
KC Thermocouple Type K, -347°C to
1372°C.
KF Thermocouple Type K, -408°F to
2501°F.
TC Thermocouple Type T, -257°C to
400°C.
TF Thermocouple Type T, -430°F to
752°F.
EC Thermocouple Type E, -240°C to
1000°C.
EF Thermocouple Type E, -400°F to
1830°F.
NC Thermocouple Type N, -240°C to
1000°C.
NF Thermocouple Type N, -410°F to
2370°F.
SC Thermocouple Type S, -46°C to
1768°C.
SF Thermocouple Type S, -51°F to
3214°F.
RC Thermocouple Type R, -45°C to
1768°C.
RF Thermocouple Type R, -49°F to
3213°F. |
NC |
RTDs
(100 Ohm Platinum)
P385C
RTD Alpha .00385, -202°C
to 850°C.
P385F
RTD Alpha .00385,
-331°F to 1562°F.
P392C
RTD Alpha .003925,
-202°C to 631°C.
P392F
RTD Alpha .003925,
-331°F to 1168°F. |
NC |
| Note:
The same temperature signal conditioner board can be user configured for all thermocouple
and RTD types listed. Temperatures for each type are spanned by a single range. |
|
Load
Cells (6-wire ratio)
WM Default Scaling. 0-20 mV = 0-100.00.
WM1 Custom
Scaling.
In the write-in field of your invoice, specify min input, min reading; max input, max
reading. Full-scale input is 20-500 mV. Excitation is 10 V for up to four 350-ohm load
cells. |
$55 |
Add-on
Options |
EB Extra Bright Red LED Display.
BL Blank Lens without Button Pads.
CBL01 RJ11-to-DB9 Cable.
CBL02 USB-to-DB9 Adapter.
BOX1 NEMA-4 enclosure, 1 cutout.
BOX2
NEMA-4 enclosure plus IPC.
IPC
Splash-proof cover. |
Unselected.
Unselected.
Unselected.
Unselected.
Unselected.
Unselected.
Unselected. |
$30
NC
$19
$39
$140
$180
$40 |